No. Technical Requirements / Parameters Unit Specification
1 Density (at 20±2°C) g/cm³ ≥ 2.15
2 Water Absorption % ≤ 0.05
3 Tensile Strength MPa ≥ 1260
4 Tensile Modulus kN/mm² ≥ 56
5 Flexural Strength MPa ≥ 900
6 Compressive Strength MPa ≥ 590
7 Torsional Strength N/mm² ≥ 90
8 Hot Flexural Strength (at 150°C) MPa ≥ 300
9 Dye Penetration Test min ≥ 15
10 Water Diffusion Test (1% NaCl boiling 100h, 12kV, 1 min) μA ≤ 100
11 Power Frequency Breakdown Voltage kV/cm ≥ 56
12 Full-wave Impulse Voltage kV/cm ≥ 95
13 Heat Deflection Temperature (HDT) °C ≥ 155

Applicable Standards: